HVAC
Bonded Logic Natural Fiber Duct Liner for use in HVAC systems is made from post-consumer recycled denim that is thermally bonded to create a high-performance insulation. Natural Fiber Duct Liner offers superior sound absorption and energy saving thermal performance, while contributing to healthy indoor air quality. The air stream surface of the Natural Fiber Duct Liner is overlaid with a durable and fire-resistant black facing that provides additional strength to the product, minimizing the potential for fiber presence in the airstream.
Natural Fiber Duct Liner contains no fiberglass and does not pose any VOC or off-gassing concerns. The insulation and the facing are treated with a non-toxic solution that actively inhibits the growth of mold, mildew, bacteria and fungi.
Uses
Natural Fiber Duct Liner is used primarily as an acoustical liner designed for HVAC sheet metal ducts to absorb unwanted noise from multiple sources and reduce heat gain or loss.
Product Features
- Class-1 Fire Rating
- Excellent Noise Absorption
- Low Air Resistance
- Resists Microbial Growth
- No Itch or Skin Irritation
Supporting Materials
Standard Available Sizes
| Thickness | Length | Width | Density | |||
|---|---|---|---|---|---|---|
| Inches | Millimeters | Feet | Meters | Inches | Millimeters | |
| .5 | (13) | 100 | (30.48) | 47-59 | (1194-1499) | 3.0 |
| 1 | (25) | 50 | (15.24) | 47-59 | (1194-1499) | 1.5 |
| 2 | (51) | 25 | (7.62) | 47-59 | (1194-1499) | 1.5 |
Acoustical Performance Sound Absorption was tested in accordance with ASTM C 423 using a type A mounting per ASTM E 795
| Product | Absorption Coefficients & Octave Band Frequencies (Hz) | |||||||
|---|---|---|---|---|---|---|---|---|
| Thichness (in) | 125 | 250 | 500 | 1000 | 2000 | 4000 | NRC | |
| 1 | (25) | .07 | .33 | .72 | .99 | .93 | .96 | .75 |
Thermal Performance* Tested in accordance with ASTM C 518
| Product | K-Value | C-Value | R-Value | ||||
|---|---|---|---|---|---|---|---|
| Thickness Inch (mm) |
Btu·in/(h·ft2·°F) | W/(m·°C) | Btu/(h·ft2·°F) | W/(m2·°C) | R | (m2·°C)/W | |
| ½ | (13) | .26 | .037 | .52 | 2.95 | 2.0 | .36 |
| 1 | (25) | .26 | .037 | .26 | 1.48 | 4.0 | .72 |
| 1½ | (38) | .26 | .037 | .17 | .97 | 6.0 | 1.08 |
| 2 | (51) | .26 | .037 | .13 | .74 | 8.0 | 1.44 |
| *Thermal conductance (C) and resistance (R) values are derived from the material thermal conductivity (k) value. | |||||||
Physical Properties
| Properties | Performance | Test Method |
|---|---|---|
| Operating Limits Temperature Velocity | Maximum:250° (121°C)5000 fpm | ASTM C 411 ASTM C 1071 |
| Surface Burning Characteristics (Fire Hazard Classification) |
Flame Spread Max: 25 Smoke Developed Max: 50 Class A / Class 1 |
ASTM E 84 UL 723 NFPA 255 |
| Corrosion Resistance | Pass - Non Corrosive | ASTM C 739 |
| Fungi Resistance | Pass - No Growth | ASTM G 21 |
| Bacteria Resistance | Pass - No Growth | ASTM G 72 |
Product Compliances UltraTouch has physical properties that meet the following current requirements, specifications, standards and codes:
| Fire Safety Standards | Building Codes |
|---|---|
| NFPA 90A - Installation of Air Conditioning and Ventilating Systems | ICBO - Iternational Conference of Building Codes |
| NFPA 90B - Installation of Warm Air Heating and Air Conditioning Systems | BOCA - Building Officials and Code Administrators |
| CABO - Council of American Building Officials | |
| SBCCI - Southern Building Code Congress International |